Hardware Preparation and Installation

ATCA-F120 Installation and Use (6806800D06J)

27

2.3.2

Power Requirements

Make sure that the blade is used in an AdvancedTCA shelf connected to -48VDC up to -60VDC,
according to Telecommunication Network Voltage (TNV-2). A TNV-2 circuit is a circuit whose
normal operating voltages exceed the limits for a safety-extra-low-voltage (SELV) under
normal operating conditions, and which is not subject to over-voltages from
telecommunication networks.

Table 2-2 Critical Temperature Limits

Location

Temperature in Celsius

Temperature in
Fahrenheit

Description

1

85°C

185°F

Top center of DC/DC converter used
for management power

2

100°C

212°F

PCB surface of main DC/DC
converter

3

105°C

221°F

Big capacitor, margin which faces
the DC/DC converter

4

90°C

194°F

Top center of filter coil

Table 2-3 DC System Power Requirements

Feature

Value

Rated voltage

-48VDC to -60VDC
US and Canada: -48VDC

Operating voltage

-40.0VDC to -72VDC
US and Canada: -40.0 to -60VDC

Input current

max. 5.0A@40V

Power dissipation

max. 200W
The tested blade was a ATCA-F120 blade, including two
installed AMC modules (35W each), and an RTM-ATCA-
F120-COP (30W).