beautypg.com

Command list, Instrument specific commands – AMETEK XDL Series II User Manual

Page 37

background image

36

is ignored except in command identifiers. e.g. '*C LS' is not equivalent to '*CLS'.

is defined as character codes 00H to 20H inclusive with the exception of the NL

character (0AH).

The high bit of all characters is ignored.

The commands are case insensitive.

Command List

This section lists all commands and queries implemented in this instrument. The commands are
listed in alphabetical order within the function groups.

Note that there are no dependent parameters, coupled parameters, overlapping commands,
expression program data elements or compound command program headers; each command is
completely executed before the next command is started. All commands are sequential and the
operation complete message is generated immediately after execution in all cases.

The following nomenclature is used:

A number in any format. e.g. 12, 12·00, 1·2 e1 and 120 e-1 are all accepted as the
number 12. Any number, when received, is converted to the required precision
consistent with the use then rounded up to obtain the value of the command.

A number with no fractional part, i.e. an integer.

A number in fixed point format e.g. 11·52, 0·78 etc.

The number of the output or status register to which the command relates.
Note that on single output supplies =1 always.
Note also that = 3 refers to the AUX output. The AUX output has limited remote
control functionality. For clarity, the commands where = 3 can be used are
explicitly commented; elsewhere only = 1 or = 2 can be used.

The commands which begin with a

*

are those specified by IEEE Std. 488.2 as Common

commands. All will function when used on the other interfaces but some are of little use.

Instrument Specific Commands

For commands specified as 'WITH VERIFY' the operation is completed when the parameter being
adjusted reaches the required value to within ±5% or ±10 counts, whichever is the greater. If the
value fails to settle within these limits within 5 seconds then the Verify Timeout bit (bit 3) is set in
the Standard Event Status Register and the operation is completed at the end of the timeout
period.

The Operation Complete bit (bit 0) in the Standard Event Status Register is only ever set by the
*OPC command. The *OPC (or the *OPC?) command can be used for device synchronisation
due to the sequential nature of remote operations.

When the supply is operated in LINK mode, commands which set values and ranges are applied
to outputs 1 and 2 simultaneously, regardless of the whether is set to 1 or 2. When the
command requests verification then verification will be sought from both outputs before the
command is completed. Additionally the SAV and RCL commands operate on non-volatile
memory reserved for linked mode set-ups and may be set to 1 or 2 with the same effect.
Note however that is part of the command header and must be included.

V

Set output to Volts. For AUX output =3

VV

Set output to Volts with verify. For AUX output =3

OVP

Set output over voltage protection trip point to Volts

I

Set output current limit to Amps