beautypg.com

Ethernet communication module dvpen01-sl – Delta Electronics Ethernet Communication Module DVPEN01-SL User Manual

Page 14

background image

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

12

C R # 11 6 :

Modbus TCP Status

Explanations:

Displaying the current communication status of Modbus TCP mode. When the CR value is set

as”0” Æ the data have not yet been received; when the CR value is set as “1” Æ the data

exchange is in progress; when the CR value is set as “2” Æ the data exchange is successful;

when the CR value is set as “3” Æ the data exchange fails.

CR value

Data exchange status

0

The data have not been received.

1

The data exchange is in progress.

2

The data exchange is successful.

3

The data exchange fails.

C R # 11 7 , 11 8 :

Modbus TCP Destination IP

Explanations:

Setting up the destination IP address in Modbus TCP mode. See explanations on CR#70 and

#71 for how to set.

C R # 11 9 :

Modbus TCP Data Length

Explanations:

Setting up the length of communication data in Modbus TCP mode. Length for 8-bit mode: K1

~K100; length for 16-bit mode: K1 ~ K200.

C R # 1 2 0 ~ 2 1 9 :

Modbus TCP Data Buffer

Explanations:

Buffer for transmitted/received data in Modbus TCP mode.

C R # 2 5 1 :

Error Code

Explanations:

Table of error code:

Bit No.

Error

b0

The network is not yet connected.

b1

Incorrect IP setting

b2

CR#13 is set as “transmitting data”, but the data exchange

is forbidden.

b3

CR#13 is set as “transmitting data”, but the data exchange

mode has not yet been enabled.

b4 NTP-Server

connection

fails.

b7

SMTP-Server connection fails.

b8

DHCP has not obtained the correct network parameter.

4.3 Numbering of Left-Side Extension Modules

After DVPEN01-SL is installed properly, you need to compile the PLC program to control the extension

modules. PLC offers FROM instrcution (for reading) and TO instrcution (for writing) to control the control