Ethernet communication module dvpen01-sl – Delta Electronics Ethernet Communication Module DVPEN01-SL User Manual

Page 11

background image

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

9

CR value

E-Mail status

10

Fail to connect to SMTP-Server

11

Incorrect recipient E-Mail address

12

SMTP-Server communication error

13

Exceeding the max. number of TCP connection

3 ~ 9, 14 ~ 255

Reserved

C R # 9 ~ 1 2 :

E-Mail 1 ~ 4 Additional Message

Explanations:

The user fills in the code, and the code will be stored in the title of the E-Mail and sent out with the

E-Mail.

„

Data Exchange

C R # 1 3 :

Data Exchange Trigger

Explanations:

When the CR is set as “0”, the data in data exchange area will not be transmitted. When the CR is

set as “1”, the data in data exchange area will be transmitted.

C R # 1 4 :

Data Exchange Status

Explanations:

When the CR is set as “0”, the data have not yet been received. When the CR is set as “1”, the

data exchange is in progress. When the CR is set as “2”, the data exchange is successful. When

the CR is set as “3”, the data exchange fails.

CR value

Status

0

Data have not yet been received.

1

Data exchange is in progress.

2

Data exchange is successful.

3

Data exchange fails.

C R # 2 5 , 2 6 :

Destination IP

Explanations:

To set up the Slave IP address for data exchange manually, write “0” into CR#28 first before

setting up the destination IP. See explanations on CR#70 and #71 for how to set.

C R # 2 8 :

Destination Slave ID

Explanations:

When you set up the Salve ID (i.e. K1 ~ K255) for data exchange, DVPEN01-SL will

automatically search for the corresponding IP address from the Slave IP list. For example, if the

ID is set as “0”, the value in CR#25 and #26 will be regarded as the destination IP.

C R # 2 9 ~ 4 8 :

Data Transmission Buffer

Explanations: