SCS-1R Installation Guide
26
OPERATOR’S GUIDE
CRC ERROR CHECK?
NO YES
CRC Error Check
Press the far right Select key for YES, which allows each message sent to the host to be
prefixed with an SIA CIS CRC-16. The format is 4 hexadecimal characters. Default is NO.
SEQUENCE NUMBER?
NO YES
Sequence Number
Press the far right Select key for YES, which sends each message sent to the host with a
sequence number ranging from 1 to 99. Default is NO.
TEST INTERVAL
MINUTES: 1
Test Interval
Press any top row Select key to clear the display and enter the new Test Interval. Enter
the number of minutes, 1 through 60, between communication test messages (S99) of
the SCS-1R Receiver and host computer. Default is 1.
ACKNOWLEDGE
TIMEOUT: 3
Acknowledge Timeout
Press any top row Select key to clear the display and enter the new Acknowledge
Timeout. This is the time in seconds, 1 through 15, the SCS-1R waits for a host
acknowledgment of a message before transmitting it again. Default is 3.
LINE NUMBER
LENGTH: 0
Line Number Length
Press any top row Select key to clear the display and enter the new Line Number
Length. Enter the number of decimal ASCII characters, 0 (zero) through 2, used to
report the SCS-1R Receiver signal line number. If 0 (zero), no information is sent. If 1,
display card number. If 2, display card and line number. Default is 0 (zero).
RETRIES TO
FAILURE: 3
Retries to Failure
Press any top row Select key to clear the display. Enter the number of attempts, between
1 and 15, the SCS-1R makes to transmit a message to the host computer. When this
number is reached, the SCS-1R begins manual acknowledgement operation. Default is 3.
Serial Ports
The SCS-1R Serial Ports section allows you to make adjustments to the Host Output, Activity Log, and Print
Operation Serial Port.
SCS-1R MENU
SERIAL PORTS
Serial Ports
Press any top row Select key to program the Serial Port settings. Press the COMMAND
key to advance to the next programming section. Press the Back Arrow key to return to
the previous section.
HOST OUTPUT BAUD
RATE: 9600
Host Output Baud Rate
Press any top row Select key to change the Host Output Baud Rate. Enter 300, 600, 1200,
2400, 4800, 9600, 19200, or 38400. Press the Command button to accept. Default is 9600.
ACTIVITY LOG BAUD
RATE: 1200
Activity Log Baud Rate
Press any top row Select key to change the Activity Log Baud Rate. Enter 300, 600, 1200,
2400, 4800, 9600, 19200, or 38400. Press the Command button to accept. Default is 1200.
PRINT OPERATION:
ALWAYS
Print Operation
Press any top row Select key to change the Print Operation. Select ALWAYS to enable
the Activity Log output for all system events. Select NEVER to disable the Activity Log.
Select FAIL to enable only when Host Automation has failed and is not acknowledging
messages from the receiver.
Note: If Print Operation is set to Always or Primary Fail, ensure that a printer is
connected to the printer port.
Set System Time/Date
This section allows you to set the correct time and date on the SCS-1R. All changes made in this section print to the
Activity Log printer. The time entered here is sent to panels if the Time Change programming option is set to YES.
SCS-1R MENU
TIME/DATE
Time/Date
Press any top row Select key to display the time and date. Press the COMMAND key to
advance to the next section of programming.
TUE 12:05 PM
04/07/09
Current Time/Day/Date
Press any select key to program the time and/or date. Press the Back Arrow key to
return to the previous display.
SET TIME/DATE
TIME DATE
Set Time/Date
Press the top row Select key under the item you would like to change. For example,
press the far left Select key to change the SCS-1R time.
ENTER TIME:
- : AM PM
Time
Press any top row Select key to enter the new time. Using the Digit keys on the
keypad, enter the current time and then press Select key under AM or PM. TIME
CHANGED displays after the time has been changed.
PRINT OPERATION
ALWYS NEVER FAIL