beautypg.com

Serial ports, Set system time/date – DMP Electronics Security Control Receiver SCS-1R User Manual

Page 31

background image

Digital Monitoring Products

SCS-1R Installation Guide

26

OPERATOR’S GUIDE

CRC ERROR CHECK?

NO YES

CRC Error Check

Press the far right Select key for YES, which allows each message sent to the host to be

prefixed with an SIA CIS CRC-16. The format is 4 hexadecimal characters. Default is NO.

SEQUENCE NUMBER?

NO YES

Sequence Number

Press the far right Select key for YES, which sends each message sent to the host with a

sequence number ranging from 1 to 99. Default is NO.

TEST INTERVAL

MINUTES: 1

Test Interval

Press any top row Select key to clear the display and enter the new Test Interval. Enter

the number of minutes, 1 through 60, between communication test messages (S99) of

the SCS-1R Receiver and host computer. Default is 1.

ACKNOWLEDGE

TIMEOUT: 3

Acknowledge Timeout

Press any top row Select key to clear the display and enter the new Acknowledge

Timeout. This is the time in seconds, 1 through 15, the SCS-1R waits for a host

acknowledgment of a message before transmitting it again. Default is 3.

LINE NUMBER

LENGTH: 0

Line Number Length

Press any top row Select key to clear the display and enter the new Line Number

Length. Enter the number of decimal ASCII characters, 0 (zero) through 2, used to

report the SCS-1R Receiver signal line number. If 0 (zero), no information is sent. If 1,

display card number. If 2, display card and line number. Default is 0 (zero).

RETRIES TO

FAILURE: 3

Retries to Failure

Press any top row Select key to clear the display. Enter the number of attempts, between

1 and 15, the SCS-1R makes to transmit a message to the host computer. When this

number is reached, the SCS-1R begins manual acknowledgement operation. Default is 3.

Serial Ports

The SCS-1R Serial Ports section allows you to make adjustments to the Host Output, Activity Log, and Print

Operation Serial Port.

SCS-1R MENU

SERIAL PORTS

Serial Ports

Press any top row Select key to program the Serial Port settings. Press the COMMAND

key to advance to the next programming section. Press the Back Arrow key to return to

the previous section.

HOST OUTPUT BAUD

RATE: 9600

Host Output Baud Rate

Press any top row Select key to change the Host Output Baud Rate. Enter 300, 600, 1200,

2400, 4800, 9600, 19200, or 38400. Press the Command button to accept. Default is 9600.

ACTIVITY LOG BAUD

RATE: 1200

Activity Log Baud Rate

Press any top row Select key to change the Activity Log Baud Rate. Enter 300, 600, 1200,

2400, 4800, 9600, 19200, or 38400. Press the Command button to accept. Default is 1200.

PRINT OPERATION:

ALWAYS

Print Operation

Press any top row Select key to change the Print Operation. Select ALWAYS to enable

the Activity Log output for all system events. Select NEVER to disable the Activity Log.

Select FAIL to enable only when Host Automation has failed and is not acknowledging

messages from the receiver.
Note: If Print Operation is set to Always or Primary Fail, ensure that a printer is

connected to the printer port.

Set System Time/Date

This section allows you to set the correct time and date on the SCS-1R. All changes made in this section print to the

Activity Log printer. The time entered here is sent to panels if the Time Change programming option is set to YES.

SCS-1R MENU

TIME/DATE

Time/Date

Press any top row Select key to display the time and date. Press the COMMAND key to

advance to the next section of programming.

TUE 12:05 PM

04/07/09

Current Time/Day/Date

Press any select key to program the time and/or date. Press the Back Arrow key to

return to the previous display.

SET TIME/DATE

TIME DATE

Set Time/Date

Press the top row Select key under the item you would like to change. For example,

press the far left Select key to change the SCS-1R time.

ENTER TIME:

- : AM PM

Time

Press any top row Select key to enter the new time. Using the Digit keys on the

keypad, enter the current time and then press Select key under AM or PM. TIME

CHANGED displays after the time has been changed.

PRINT OPERATION

ALWYS NEVER FAIL