Page 27

background image

Digital Monitoring Products

SCS-1R Installation Guide

22

OPERATOR’S GUIDE

Enter the new Receiver Key up to eight characters long. Press the COMMAND key to

display the next prompt.

CHANGE REC KEY

SURE? YES NO

Change Receiver Key

After entering the desired Receiver Key and pressing COMMAND, the SURE? YES NO

prompt displays. Press the Select key under YES to keep the new key, or under NO to

use the previously stored key.

RECEIVER KEY

CHANGED

Receiver Key Changed

After pressing the Select key under YES, the display indicates that the receiver key has

been successfully changed.

RECEIVER HOURS

FROM GMT: 6

Receiver Hours From GMT

Number of hours (0 to 23), from the Greenwich Time zone (GMT), where the receiver is

located. Refer to the table below for various cities and GMT settings. Default is 6.

GMT

City/Time Zone

GMT

City/Time Zone

0

London, Monrovia, Lisbon, Dublin, Casablanca, Edinburgh

13

New Cadelonia

1

Cape Verde Island, Azores

14

Guam, Sydney

2

Mid-Atlantic, Fernando de Noronha

15

Tokyo, Seoul

3

Buenos Aires, Georgetown, Brasilia, Rio de Janeiro

16

Hong Kong, Singapore

4

Atlantic Time (Canada), Caracas, La Paz, Santiago

17

Bangkok, Hanoi

5

Eastern Time (US, Canada) Bogota, Lima, Arequipa

18

Dhaka, Almaty

6

Central Time (US, Canada), Mexico City, Saskatchewan

19

Islamabad, Karachi

7

Mountain Time (US, Canada), Edmonton

20

Abu Dhabi, Kazan

8

Pacific Time (US, Canada), Tijuana

21

Moscow, Bagdad

9

Alaska

22

Eastern Europe

10

Hawaii

23

Rome, Paris, Berlin

11

Midway Island, Samoa

12

Fiji, Marshall Island, Wellington, Auckland, Kwajalein, Kamchatka

DIALER LINE

MONITOR? NO YES

Dialer Line Monitor

Press the far right Select key for YES to enable monitoring of digital dialer lines for

any failed communication attempts. A failed communication attempt occurs when the

line card goes off hook but does not successfully communicate with a panel. Press the

middle right Select key for NO, to disable the line monitoring operation. Default is NO.
When enabled, and a line communication fails, an S153 Communication Trouble

message, along with the card and line number, is sent to the host automation computer,

SCS-1R printer and LCD display. Manual acknowledgement is required when the SCS-1R

is not successfully communicating with the host automation computer.

EVENT DISPLAY

PRIORITY STD

Event Display Priority

For Canadian Central Stations that receive signals from a ULC-599-04 fire communicator

installation, set the Event Display priority to ULC. Otherwise, set to STD. This option

defines the priority of messages waiting for manual acknowledgement in event memory

when the receiver is unable to communicate with the host automation computer.
To change the setting, press a top row key. Select STD to have the display follow the

standard priority as shown below. Select ULC to have the display follow the ULC priority

shown below for Canadian fire communicator installations. Default is STD.

Priority Number

STD

ULC

1

Fire Alarms

Fire Alarms

2

Burglary Alarms

Fire Supervisory

3

Trouble, Fire Supervisory, & Fire Trouble

Fire Trouble

4

Other Messages

Burglary Alarms & Trouble

5

N/A

Other Messages

LOCAL IP ADDRESS

192.168.000.250

Local IP Address

Enter the LOCAL IP ADDRESS of the SCS-150 processor. The Local IP Address must

be unique and cannot be duplicated and needs to be a privately accessible network

connection. The default value is 192.168.000.250.

LOCAL PORT

2001

Local Port

The LOCAL PORT identifies the SCS-150 IP port used when the host automation

computer communicates with the receiver over network. If a setting change is

required, enter the new number. Valid range is 1 to 65,535. The default value is 2001.

GATEWAY ADDRESS

000.000.000.000

Gateway Address

Enter the local SCS-150 GATEWAY ADDRESS. You need the SCS-150 Gateway Address if

subnets are divided in your network. The default value is 000.000.000.000.

STD ULC