DMP Electronics Security Control Receiver SCS-1R User Manual
Page 27
Digital Monitoring Products
SCS-1R Installation Guide
22
OPERATOR’S GUIDE
Enter the new Receiver Key up to eight characters long. Press the COMMAND key to
display the next prompt.
CHANGE REC KEY
SURE? YES NO
Change Receiver Key
After entering the desired Receiver Key and pressing COMMAND, the SURE? YES NO
prompt displays. Press the Select key under YES to keep the new key, or under NO to
use the previously stored key.
RECEIVER KEY
CHANGED
Receiver Key Changed
After pressing the Select key under YES, the display indicates that the receiver key has
been successfully changed.
RECEIVER HOURS
FROM GMT: 6
Receiver Hours From GMT
Number of hours (0 to 23), from the Greenwich Time zone (GMT), where the receiver is
located. Refer to the table below for various cities and GMT settings. Default is 6.
GMT
City/Time Zone
GMT
City/Time Zone
0
London, Monrovia, Lisbon, Dublin, Casablanca, Edinburgh
13
New Cadelonia
1
Cape Verde Island, Azores
14
Guam, Sydney
2
Mid-Atlantic, Fernando de Noronha
15
Tokyo, Seoul
3
Buenos Aires, Georgetown, Brasilia, Rio de Janeiro
16
Hong Kong, Singapore
4
Atlantic Time (Canada), Caracas, La Paz, Santiago
17
Bangkok, Hanoi
5
Eastern Time (US, Canada) Bogota, Lima, Arequipa
18
Dhaka, Almaty
6
Central Time (US, Canada), Mexico City, Saskatchewan
19
Islamabad, Karachi
7
Mountain Time (US, Canada), Edmonton
20
Abu Dhabi, Kazan
8
Pacific Time (US, Canada), Tijuana
21
Moscow, Bagdad
9
Alaska
22
Eastern Europe
10
Hawaii
23
Rome, Paris, Berlin
11
Midway Island, Samoa
12
Fiji, Marshall Island, Wellington, Auckland, Kwajalein, Kamchatka
DIALER LINE
MONITOR? NO YES
Dialer Line Monitor
Press the far right Select key for YES to enable monitoring of digital dialer lines for
any failed communication attempts. A failed communication attempt occurs when the
line card goes off hook but does not successfully communicate with a panel. Press the
middle right Select key for NO, to disable the line monitoring operation. Default is NO.
When enabled, and a line communication fails, an S153 Communication Trouble
message, along with the card and line number, is sent to the host automation computer,
SCS-1R printer and LCD display. Manual acknowledgement is required when the SCS-1R
is not successfully communicating with the host automation computer.
EVENT DISPLAY
PRIORITY STD
Event Display Priority
For Canadian Central Stations that receive signals from a ULC-599-04 fire communicator
installation, set the Event Display priority to ULC. Otherwise, set to STD. This option
defines the priority of messages waiting for manual acknowledgement in event memory
when the receiver is unable to communicate with the host automation computer.
To change the setting, press a top row key. Select STD to have the display follow the
standard priority as shown below. Select ULC to have the display follow the ULC priority
shown below for Canadian fire communicator installations. Default is STD.
Priority Number
STD
ULC
1
Fire Alarms
Fire Alarms
2
Burglary Alarms
Fire Supervisory
3
Trouble, Fire Supervisory, & Fire Trouble
Fire Trouble
4
Other Messages
Burglary Alarms & Trouble
5
N/A
Other Messages
LOCAL IP ADDRESS
192.168.000.250
Local IP Address
Enter the LOCAL IP ADDRESS of the SCS-150 processor. The Local IP Address must
be unique and cannot be duplicated and needs to be a privately accessible network
connection. The default value is 192.168.000.250.
LOCAL PORT
2001
Local Port
The LOCAL PORT identifies the SCS-150 IP port used when the host automation
computer communicates with the receiver over network. If a setting change is
required, enter the new number. Valid range is 1 to 65,535. The default value is 2001.
GATEWAY ADDRESS
000.000.000.000
Gateway Address
Enter the local SCS-150 GATEWAY ADDRESS. You need the SCS-150 Gateway Address if
subnets are divided in your network. The default value is 000.000.000.000.
STD ULC