Examples – Pilz PSS SB NOT, Basic license User Manual
Page 96

8-12
Examples
Modular Block System: Emergency Stop Circuits
Fig 8-11: Wiring diagram
Feedback loop monitoring (shutdown with two main contactors
connected in series and pulsed outputs), category 4
Block: SB067/RFK_K4
INFORMATION
If wired outside the control cabinet, or if there is any possibility of a short
circuit, the feedback loops must be allocated pulsed outputs (A0.16 and
A0.17); this must be entered in the configurator (DB002).
L1
24 V
N
M1
K-M1.2
K-M1.1
RFK
K-M1.1
RFK
K-M1.2
M1
START
E0.01
E0.02
E0.08
PSS
+ A1.16 -
K-M1.1
K-M1.2
A0.16 A0.17
pulsed outputs
M
This manual is related to the following products:
- PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB HYD, Basic license PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license