Sb067: feedback loop monitoring, Block header, Input parameters – Pilz PSS SB NOT, Basic license User Manual
Page 70: Output parameters, Standard function blocks sb067

6-28
Modular Block System: Emergency Stop Circuits
Standard Function Blocks
SB067
SB067: Feedback loop monitoring
Block header
Input parameters
•
SSNR:
Safety subroutine number
Permitted value range: 1 ... 200
Format: Byte constants KB001 ... KB200
(see sections in Chapter 5 entitled “Administration data blocks
DB015, DB016 and DB017” and “Input parameter SSNR”).
•
RFK1:
Feedback loop N/C contact on contactor 1
•
RFK2:
Feedback loop N/C contact on contactor 2
•
RSET:
Reset input
RSET = 0/1 signal edge: Trigger reset
•
Ein:
Switches on main contactor via output parameter
K
Ein = 0/1-signal edge: Switch on output parameter K (K = 1)
Ein = 1/0-signal edge: Switch off output parameter K (K = 0)
Input circuitry
If you are only using one feedback loop, connect the RFK input to
RFK1
and
RFK2.
Output parameters
•
FG:
Enable bit
FG = 0: Not enabled
FG = 1: No error found on this relay block function
•
K:
Output to main contactor
SB 067
RFK_K4
B - SSNR
X - RFK1
X - RFK2
X - RSET
X - Ein
FG - X
K
- X
- PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB HYD, Basic license PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license