Modular Block System: Emergency Stop Circuits
Standard Function Blocks
- Bit 03:
With: “Automatic reset (PSS cold start)”:
E-STOP button operated and reset button pressed
Remedy: Check button, cable and input card, release E-STOP
button and reset again (input parameter
EIN).
With: “Automatic reset when E-STOP button is released”:
E-STOP button operated
Remedy: Release E-STOP button
- Bit 08:
E-STOP released, ready for reset
Remedy: Press reset button (input parameter
EIN)
- Bit 09:
Reset button pressed constantly (i.e. stuck in)
Remedy: Check button, cable and input card, release E-STOP
button and reset again (input parameter
EIN)
- Bit 10:
Reset successful, but N/C contact S1_Ö failed to open when
the E-STOP button was operated.
Remedy: Press E-STOP button again to ensure that contacts
open correctly and then reset; otherwise: check cable and
input card, release the E-STOP button and reset (input
parameter
EIN)
- Bit 11:
Reset successful, but N/C contact S2_Ö failed to open when
the E-STOP button was operated.
Remedy: Press E-STOP button again to ensure that contacts
open correctly and then reset; otherwise: check cable and
input card, release the E-STOP button and reset (input
parameter
EIN)
• Error messages on the CPU-display
- E 001:
Parameter error
SSNR does not lie within the limits of 1 ... 200
SB061
- PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB HYD, Basic license PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license