Modular Block System: Emergency Stop Circuits

Standard Function Blocks

Sequence of function test:
• Press E-STOP button

• Release E-STOP button

• Press reset button (input parameter

RSET)

Error messages

Any fault that is detected will be stored in the corresponding error data
word (

SSNR) of the administration data block (1st data block), until the

fault has been fully dealt with.

• Error messages in the administration data block

- Bit 00:

E-STOP button operated
Remedy: Release E-STOP button and reset
(input parameter

RSET)

- Bit 01:

Reset required
Remedy: Reset (input parameter

RSET)

- Bit 03:

Function test required due to a synchronisation error
Remedy: Perform function test (press E-STOP button, release
it and reset (input parameter

RSET))

- Bit 04:

E-STOP button operated and reset button pressed
Remedy: Check button, cable and input card, release E-STOP
button and reset again (input parameter

RSET)

- Bit 05:

Reset button pressed too soon or constantly pressed
Remedy: Check reset button, cable and input card and reset
again (input parameter

RSET)

- Bit 06:

Initial reset required
Remedy: Reset (input parameter

RSET)

- Bit 07:

Synchronisation error N/C contact 1
Remedy: Check button, cable and input card, release the E-
STOP button and perform a function test (press E-STOP
button, release it and reset (input parameter

RSET))

SB063