Changes to the standard function blocks, Sb060: emergency stop monitoring, Sb061: emergency stop monitoring – Pilz PSS SB NOT, Basic license User Manual
Page 107

9-3
Modular Block System: Emergency Stop Circuits
Changes to the standard function blocks
INFORMATION
When imported into existing projects, new parameters must be set for
standard function blocks in which input or output parameters have been
amended (additional I/O parameters, notation changed, description
changed etc.).
Please note:
STOP
An SB version marked with this symbol can only replace the
previous SB version in an existing application program if new
parameters are set for it once imported.
SB060: Emergency stop monitoring
Version
Date
CRC
1.0
13.03.96
4001
• No changes made.
SB061: Emergency stop monitoring
Version
Date
CRC
1.0
13.03.96
4AC8
1.1
07.01.97
D4F9
Changes from Version 1.0 to Version 1.1
• If “automatic reset” is selected (input parameter
EIN = 1 and QAut = 1),
the application program no longer locks up if the E-STOP button is
pressed and then released in quick succession.
Previously this could only be rectified by switching the controller off and
then on again.
- PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB HYD, Basic license PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license