Modular Block System: Emergency Stop Circuits
• If wiring is to be laid outside the control cabinet, feedback loops must use
test pulses.
• Feedback loops must use test pulses if the possibility of a short-circuit
cannot be excluded.
• If only one contactor is used to switch a potentially dangerous drive, it
must be possible to switch this off via a group contactor within the
current path (selective shutdown).
• The group contactor must also be monitored through a feedback loop.
SB067: Feedback loop monitoring
SB067 is a standard function block for the direct control and monitoring of
contactors up to category 4, in accordance with EN 954-1, 03/97.
Features and application areas:
• Feedback loop is monitored during the change in the enable flag and
while the contactor is in a static condition.
• Feedback loop can be monitored on two separate feedback loops of
main contactors connected in series.
• Feedback loop can be monitored on group contactors.
INFORMATION
Input circuitry:
• To achieve category 4, two independent shutdown routes must be
provided within the current path of the potentially dangerous drive.
• If wiring is to be laid outside the control cabinet, feedback loops must use
test pulses.
• Feedback loops must use test pulses if the possibility of a short-circuit
cannot be excluded.
• If only one relay is used to switch a potentially dangerous drive, it must
be possible to switch this off via a group contactor located within the
current path (selective shutdown).
• The group contactor must also be monitored through a feedback loop.
- PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB HYD, Basic license PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license