3 connection to a control system, Connection to a control system – Pilz PIT m3.2p machine tools pictogram User Manual
Page 44

Wiring
Operating Manual PIT m3.2p
1003176EN02
44
6.3
Connection to a control system
Depending on the application area and its respective regulations, the operating mode se
lector switch can be used up to SIL CL 2 (EN IEC 62061) and up to PL d
(EN ISO 138491), if the operating modes are evaluated by a safety control system with
safe "1oon" evaluation.
The examples below meet the following conditions:
}
A PNOZ m1p is used as a safety control system.
}
An "operating mode selector switch" function element is configured in the PNOZmulti
Configurator for safe "1oon" evaluation.
}
The Key ID interface and the interface for status information are evaluated via a higher
level process control system.
}
The cables for the unit's supply voltage (A1, A2) contain a 4 A fuse, characteristic B/C.