beautypg.com

3 connection to a control system, Connection to a control system – Pilz PIT m3.2p machine tools pictogram User Manual

Page 44

background image

Wiring

Operating Manual PIT m3.2p
1003176­EN­02

44

6.3

Connection to a control system

Depending on the application area and its respective regulations, the operating mode se­
lector switch can be used up to SIL CL 2 (EN IEC 62061) and up to PL d
(EN ISO 13849­1), if the operating modes are evaluated by a safety control system with
safe "1oon" evaluation.

The examples below meet the following conditions:

}

A PNOZ m1p is used as a safety control system.

}

An "operating mode selector switch" function element is configured in the PNOZmulti
Configurator for safe "1oon" evaluation.

}

The Key ID interface and the interface for status information are evaluated via a higher­
level process control system.

}

The cables for the unit's supply voltage (A1, A2) contain a 4 A fuse, characteristic B/C.

This manual is related to the following products: