2 control program requirements, Control program requirements – Pilz PIT m3.2p machine tools pictogram User Manual
Page 27
![background image](https://www.manualsdir.com/files/762816/content/doc027.png)
Function description
Operating Manual PIT m3.2p
1003176EN02
27
4.2.2
Control program requirements
In order to achieve SIL CL 2 (EN IEC 62061)/PL d (EN ISO 138491) in an application, the
evaluation must be carried out by a safetyrelated function block. The safetyrelated func
tion block must meet the following requirements:
}
The function block must enable safe "1oon" evaluation of the output signals at SOM1 ...
SOM5.
}
If two or more operating modes are present at the same time, this must be detected as
an error.
INFORMATION
The function block must bridge the t1 switchover delay (see
).
If a PNOZmulti (e.g. PNOZ m1p) is used as the safety control system in
conjunction with an "operating mode selector switch" function element, then
this requirement is met automatically.