Analogue value and typical digital value with a current range of
0 ... 20 mA plus default values:
Analogue value and typical digital value with a current range of
4 ... 20 mA plus default values:
4.2.3.4
User scaling
User scaling
4-
][Funktionsbeschreibung_BA_Konfig Skalier Anwend Aus
User scaling is an additional scaling level prior to manufacturer scaling.
You can use this scaling to correct local influences. The function is the
same as that of manufacturer scaling:
y = (a
2
/ 256
D
* x) + b
2
or
y = (a
2
/ 100
H
* x) + b
2
a
2
= Amplification factor * 256
D
User scaling is deactivated in the default setting. The default value for
offset is 0. The default value for gain is 256
D
(100
H
). That corresponds
to amplification factor 1.
Analogue value of current
Decimal digital value
0 mA
0
10 mA
16 384
20 mA
32 767
Analogue value of current
Decimal digital value
4 mA
0
12 mA
16 384
20 mA
32 767
10 mA
12 mA
14 mA
16 mA
18 mA
8 mA
6 mA
4 mA
2 mA
0 mA
20 mA
32 767
29 490
26 214
22 937
19 660
16 384
13 107
9 830
6 553
3 277
0
12 mA
4 mA
20 mA
32 767
16 384
0
6 mA
4096
8 mA
8192
10 mA
12 288
14 mA
20 479
16 mA
24 575
18 mA
28 671