User scaling, 4function description, 2 configuration – Pilz PSSu E S 2AO I User Manual

Page 23

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-7

4.2

Configuration

4

Function description

Analogue value and typical digital value with a current range of
0 ... 20 mA plus default values:

Analogue value and typical digital value with a current range of
4 ... 20 mA plus default values:

4.2.3.4

User scaling

User scaling

4-

][Funktionsbeschreibung_BA_Konfig Skalier Anwend Aus

User scaling is an additional scaling level prior to manufacturer scaling.

You can use this scaling to correct local influences. The function is the

same as that of manufacturer scaling:

y = (a

2

/ 256

D

* x) + b

2

or

y = (a

2

/ 100

H

* x) + b

2

a

2

= Amplification factor * 256

D

User scaling is deactivated in the default setting. The default value for

offset is 0. The default value for gain is 256

D

(100

H

). That corresponds

to amplification factor 1.

Analogue value of current

Decimal digital value

0 mA

0

10 mA

16 384

20 mA

32 767

Analogue value of current

Decimal digital value

4 mA

0

12 mA

16 384

20 mA

32 767

10 mA

12 mA

14 mA

16 mA

18 mA

8 mA

6 mA

4 mA

2 mA

0 mA

20 mA

32 767

29 490

26 214

22 937

19 660

16 384

13 107

9 830

6 553

3 277

0

12 mA

4 mA

20 mA

32 767

16 384

0

6 mA

4096

8 mA

8192

10 mA

12 288

14 mA

20 479

16 mA

24 575

18 mA

28 671