4.2
Configuration
4
Function description
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-6
Arithmetic examples using decimal values:
The module always uses two's complement representation for internal
processing, irrespective of the configured data format. The values from
0000
H
to FFFF
H
form a number circle in the two's complement repre-
sentation. 8000
H
follows 7FFF
H
(= 32 767
D
) and is interpreted as the
lowest negative number (= -32 768
D
). 32 767
D
is never exceeded; the
value never falls below -32,768
D
.
][Funktionsbeschreibung_BA_Konfig Skalier ST 2xI
INFORMATION
With the given amplification factor, gain (a
1
) is calculated as fol-
lows:
Gain (a
1
) = Amplification factor * 256
D
Amplification by 5 % is therefore:
1.05 * 256
D
= 269
D
Digital value
before manufacturer
scaling (x)
Gain (a
1
)
Offset (b
1
)
Amplification factor
(a
1
/ 256
D
)
Value after
manufacturer scal-
ing (y)
1 000
256
0
1
1 000
1 000
512
0
2
2 000
1 000
32
0
0,125
125
1 000
269
500
1,05
1 550
1 000
128
-50
0,5
450
INFORMATION
If 7FFF
H
is exceeded as a result of scaling, unintended values
may be set on the output.