4function description, 2 configuration – Pilz PSSu E S 2AO I User Manual
Page 19
![background image](https://www.manualsdir.com/files/762748/content/doc019.png)
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-3
4.2
Configuration
4
Function description
As the module's resolution is 12 bits plus sign bit, the three least signif-
icant bits have no significance for the analogue value.
Analogue value and typical digital value with a current range of
0 ... 20 mA, two's complement or sign and magnitude representati-
on:
Analogue value and typical digital value with a current range of
4 ... 20 mA, two's complement or sign and magnitude representati-
on:
Analogue value of current
Decimal digital value
Binary digital value
Hexadecimal digital value
0 mA
0
0000 0000 0000 0000
0000
H
10 mA
16 384
0100 0000 0000 0000
4000
H
20 mA
32 767
0111 1111 1111 1111
7FFF
H
Analogue value of current
Decimal digital value
Binary digital value
Hexadecimal digital value
4 mA
0
0000 0000 0000 0000
0000
H
12 mA
16 384
0100 0000 0000 0000
4000
H
20 mA
32 767
0111 1111 1111 1111
7FFF
H