Wiring

Operating Manual PSSu E S PD-D
21975-EN-04

20

21

11

[1]

[3]

[2]

[4]

[5]

[6]

Please note:

}

The minimum cable cross section for field connection terminals on the base modules is

0.14 mm

2

(AWG26)

}

The maximum cable cross section for field connection terminals is:

– Digital inputs: 1.5 mm

2

(AWG16)

– Digital outputs: 2.0 mm

2

(AWG14)

– Inputs/outputs on the counter modules: 1.5 mm

2

(AWG16)

– Analogue inputs/outputs: 1.5 mm

2

(AWG16)

– Communication cables: 1.5 mm

2

(AWG16)

– Test pulse outputs: 1.5 mm

2

(AWG16)

– Power supply: 2.5 mm

2

(AWG12)

– Functional earth: 2.5 mm

2

(AWG12)

}

On base modules with screw terminals:

– If you use a multi-strand cable to connect the I/Os, it is recommended that you use

ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm

2

, Form A or C,

although this is not essential. To crimp the ferrules you can use crimp pliers (crimp
form A or C) conforming to EN 60947-1, such as the PZ 1.5 or PZ 6.5 from Weid-
müller, for example.

– Maximum torque setting: 0.8 Nm

}

Use copper wiring.