beautypg.com

4 function description, 1 module features, 1 function description – Pilz PSSu E S PD-D User Manual

Page 12: 2 integrated protection mechanisms, 2 configuration, 1 pssu assignment in system environment a, 1 addresses in the process image, Section 4, Function description, Module features

background image

Function description

Operating Manual PSSu E S PD-D
21975-EN-04

12

Function description

Module features

Function description

}

The module routes the periphery supply from the module bus to the base module termi-

nals.

}

The periphery supply is available at the outputs.

The module provides advanced diagnostic data, which is also available in a status byte in
the ST-PII (not in system environment B):

}

Output overload/short circuit

}

Excess module temperature

Integrated protection mechanisms

When the PSSu E F PS1(-T) is used to supply the system, the module supply is buffered
for 20 ms if the supply voltage is interrupted.
The module provides the following diagnostic data:

}

Start-up error

}

Configuration error

}

ST communication error

}

Bus termination error

}

Output overload

}

Temperature error: too warm

}

Temperature error: too hot

Configuration

PSSu assignment in system environment A

It is not necessary to configure ST outputs in the PSSuniversal Configurator on the
PSS WIN-PRO system software. Overload detection and temperature monitoring can be
configured: The entries in the status byte can be deactivated.
Further information on configuration is available in the PSSuniversal Configurator's online
help.

Addresses in the process image
The module occupies 8 consecutive bit addresses for the status byte in the ST-PII, if the
status byte is configured.

Configuration

SafetyBUS p

Standard bus system

FS-PIO

ST-PII

ST-PIO

Without status byte

- - -

- - -

- - -

With status byte ("S")

- - -