Function description

Operating Manual PSSu E F INC(­T)
1001454­EN­07

20

Key to timing diagram:

Section

Function

Procedure for PSSu in system environ­
ment B

a

Enter counter status

In the user program, assign the default
counter status to OutputData.NewCounter­
Value

b

Transfer counter status

In the user program, set Out­
putData.SetCounter

c

Acknowledge transfer

The module sets InputData.SetCounter­
Done; InputData.Underflow and In­
putData.Overflow are reset

D

Finish transfer

In the user program, reset Out­
putData.SetCounter

e

Ready for new function

The module resets InputData.SetCounter­
Done

4.2

Configuration

4.2.1

Operating modes and parameters

The module has the following configuration options:

Configuration

Default
value

Meaning

Operating mode

X

Incremental encoder mode

Counter mode

Period length measure­
ment or latch function

X

Latch function

Period length measurement

Status input

X

The status at input S is transmitted via a bit.

The status is transmitted via two redundant bits.

The status is transmitted via two diverse bits.

(1)

(1)

 Transmitting the status via two bits enables simple fault detection: Two redundant bits

must always be the same, two diverse bits must always be different, otherwise the trans­
mission is faulty.