Page 20: Operating modes and parameters

Function description
Operating Manual PSSu E F INC(T)
1001454EN07
20
Key to timing diagram:
Section
Function
Procedure for PSSu in system environ
ment B
a
Enter counter status
In the user program, assign the default
counter status to OutputData.NewCounter
Value
b
Transfer counter status
In the user program, set Out
putData.SetCounter
c
Acknowledge transfer
The module sets InputData.SetCounter
Done; InputData.Underflow and In
putData.Overflow are reset
D
Finish transfer
In the user program, reset Out
putData.SetCounter
e
Ready for new function
The module resets InputData.SetCounter
Done
4.2
Configuration
4.2.1
Operating modes and parameters
The module has the following configuration options:
Configuration
Default
value
Meaning
Operating mode
X
Incremental encoder mode
Counter mode
Period length measure
ment or latch function
X
Latch function
Period length measurement
Status input
X
The status at input S is transmitted via a bit.
The status is transmitted via two redundant bits.
The status is transmitted via two diverse bits.
(1)
(1)
Transmitting the status via two bits enables simple fault detection: Two redundant bits
must always be the same, two diverse bits must always be different, otherwise the trans
mission is faulty.