beautypg.com

4 emc-compliant wiring, Emc­compliant wiring, 4 emc­compliant wiring – Pilz PNOZ m EF 2MM User Manual

Page 18

background image

Commissioning

Operating Manual PNOZ m EF 2MM
1003107­EN­01

18

npn proximity switch with resistor R = 47 kOhm

6.4

EMC­compliant wiring

EMC­compliant wiring for connecting 2 proximity switches

PNOZ m EF 2MM

To avoid EMC interference we recommend that the shield on the encoder cables or the
housing of the shielded junction box is only connected to earth at a single point:
or B or C or D or E
Conductor loops outside the shield must be avoided.
If a shielded junction box is not used, the shield must run continuously from the encoder to
the evaluation device.