beautypg.com

1 safety characteristic data, Safety characteristic data – Pilz PNOZ m B0 User Manual

Page 35

background image

Technical details

Operating Manual PNOZ m B0
1002660­EN­03

35

8.1

Safety characteristic data

Unit

Operating
mode

EN ISO
13849­1: 2008

PL

EN ISO
13849­1: 2008

Category

EN IEC 62061

SIL CL

EN IEC 62061

PFH

D

 [1/h]

EN ISO
13849­1: 2008

T

M

 [year]

Logic

CPU

PL e

Cat. 4

SIL CL 3

4,74E­10

20

Expansion
right

PL e

Cat. 4

SIL CL 3

2,79E­11

20

Input

SC inputs

1­channel

PL d

Cat. 2

SIL CL 2

3,85E­09

20

SC inputs

2­channel

PL e

Cat. 4

SIL CL 3

7,95E­11

20

SC inputs

1­ch., pulsed
light barrier

PL e

Cat. 4

SIL CL 3

3,85E­10

20

Output

SC outputs

1­channel
with ad­
vanced fault
detection

PL e

Cat. 4

SIL CL 3

1,66E­11

20

SC outputs

1­channel

PL d

Cat. 2

SIL CL 2

1,57E­10

20

SC outputs

2­channel

PL e

Cat. 4

SIL CL 3

1,29E­10

20

All the units used within a safety function must be considered when calculating the safety
characteristic data.

INFORMATION

A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.