beautypg.com

Display elements, Display elements for device diagnostics, 7operation – Pilz PNOZms2p HTL User Manual

Page 34: 2 display elements, 1 display elements for device diagnostics

background image

7.2

Display elements

7

Operation

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

7-2

7.2

Display elements

7200

Display elements

7-

Anzeige Legende 3x

Legend:

7.2.1

Display elements for device diagnostics

Display elements for device diagnostics

7-

Betrieb_Anzeige_multi_Drehzahlwaechter_BA

LED on

LED flashes

LED off

LED

LED status

Meaning

POWER

Supply voltage is present

FAULT

External fault leading to a safe condition; the fault is at the incremental encoder in-
puts whose LEDs are flashing, e.g. short across the contacts

Internal fault leading to safe condition

SHAFT1
SHAFT2

Encoder or wiring fault

Axis 1 and/or axis 2 are in the normal range (no standstill, no overspeed)

Axis 1 and/or axis 2 signalling standstill

Axis 1 and/or axis 2 signalling overdrive

X12
X22

Incremental encoders on terminals X12 and/or X22 are connected correctly

I10, I11, I20,
I21

Proximity switch on terminal I10, I11, I20, I21 is energised