Overview, Unit structure, 1 scope of delivery – Pilz PNOZ ma1p 2 Analog Input User Manual
Page 9: 2 unit features, 2overview, 1 unit structure
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
2-1
2.1
Unit structure
2
Overview
2
2000
Overview
Overview
2-
2.1
Unit structure
2100
Unit structure
2-
2.1.1
Scope of delivery
Scope of delivery
2-
Lieferumfang_Brck_774639_modul_BA
`
Expansion modulePNOZ ma1p
`
Jumper 774 639
2.1.2
Unit features
Unit features
2-
Gerätemerkmale_Verwendung
Using the product PNOZ ma1p:
Verwendung/Bildunterschrift_multi_Modul
Expansion module for connection to a base unit from the PNOZmulti
modular safety system
Geraetemerkmale_Zusatz BA Einleitung
The product has the following features:
Gertemerkmale
`
2 safe analogue inputs for current or voltage measurement (configura-
ble)
`
Voltage range: -10,24 ... +10.2375 V
`
Current range: 0 ... 25.59 mA
`
Resolution
– Voltage measurement: 13 Bit (signed 12 Bit)
– Current measurement: 12 Bit
`
Range monitoring (4 range limits can be configured)
`
Threshold value monitoring (8 threshold values can be configured)
`
Max. 4 PNOZ ma1p units can be connected to the base unit
`
LED indicators for
– Operating status
– Status of the input signals (Ch0, Ch1)
– Errors
Geraetemerkmal_Coated Version
`
Coated version:
Increased environmental requirements