General wiring guidelines

6

Commissioning

6

6000

Commissioning

Commissioning

6-

6.1

General wiring guidelines

6100

General wiring guidelines

6-

Verdrahtung_multi_Modul

The wiring is defined in the circuit diagram of the PNOZmulti Configura-

tor.

Please note:

`

Information given in the "Technical details" must be followed.

`

Use copper wire that can withstand 75 °C.

Verdrahtung_multi_Analogeingangsmodul

`

The power supply that feeds the expansion module and the input de-

vices must meet the regulations for extra low voltages with safe sep-

aration (SELV, PELV).

`

6 connection terminals are available for each of the supply connec-

tions 24 V and 0 V. This means that the supply voltage can be looped

through several connections and the encoder can be supplied.

`

Use shielded, twisted pair cable for the connections on the input cur-

rent circuits.

`

Separate the supply voltage cable from the analogue input current

lines.

`

If the analogue input module is used to measure current, the voltage

inputs must be short-circuited.

`

For transducers located outside the control cabinet: Where the

cable enters the control cabinet, the cable shield must be connected

to the earth potential over a wide surface area and with low imped-

ance (connect in star).

NOTICE

If the analogue input module is used to measure voltage, both

inputs must be wired.