Safety, Intended use, 1 system requirements – Pilz PNOZ ma1p 2 Analog Input User Manual
Page 11: 3safety, 1 intended use
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
3-1
3.1
Intended use
3
Safety
3
3000
Safety
Safety
3-
3.1
Intended use
3100
Intended use
3-
Gertebeschreibung_Analogeingangsmodul
The expansion module is an analogue input module. It provides 2 safe
analogue inputs for current or voltage measurement. For current meas-
urement, both inputs can be used independently. For voltage measure-
ment, both inputs must always be wired. The analogue inputs are
suitable for connecting transducers or input devices with standardised
10 V voltage signals or 20 mA current signals. The analogue inputs are
designed as differential inputs. Each analogue input has a signal range
of –10 VDC to +10 VDC or 0 mA to 25 mA.
Bestimmung/Gertebeschreibung_multi_Zusatz_Modul
The expansion module may only be connected to a base unit from the
PNOZmulti modular safety system.
Bestimmung/Gertebeschreibung_multi_System
The PNOZmulti modular safety system is used for the safety-related in-
terruption of safety circuits and is designed for use on:
`
E-STOP equipment
`
Safety circuits in accordance with VDE 0113 Part 1 and EN 60204-1
Bestimmung/Gertebeschreibung_Ausschluss
Intended use includes making the electrical installation EMC-compliant.
The product is designed for use in an industrial environment. It is not
suitable for use in a domestic environment, as this can lead to interfer-
ence.
The following is deemed improper use in particular:
`
Any component, technical or electrical modification to the product
`
Use of the product outside the areas described in this manual
`
Use of the product outside the technical details (see chapter entitled
“Technical Details”)
Bestimmung/Gertebeschreibung_Zusatz_Coated Version
The coated version of the product PNOZ ma1p is suitable for use where
there are increased environmental requirements (see Technical Details).
3.1.1
System requirements
System requirements
3-
Systemvoraussetzungen_Analogeingangsmodul
`
PNOZmulti Configurator: From Version 5.3.0
`
Base unit PNOZ m1p: From Version 5.6
`
Base unit PNOZ m2p: From Version 2.6
Please contact Pilz if you have an older version.