Device properties

4

Function Description

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-2

4.1.2

Function description

Function description

4-

4.1.2.1

Operation

Operation

4-

Funktionen_multi_Analogeingangsmodul

The analogue input module monitors analogue input signals. It can

measure both current and voltage.

The input signals are collected and read in at each input through two

channels and are converted into digital signals. The resolution is 13 Bit

for voltage measurement, 12 Bit for current measurement.

In the PNOZmulti Configurator you can define limit values, which are to

be monitored:

`

Range monitoring

With range monitoring you can define the permitted value range. You

can define up to 4 range limits (e.g. < 3 mA monitored for open circuit;

I > 21 mA monitored for input device error). Depending on the select-

ed condition ("greater than" or "less than"), the ENBL output bit and

output bits 1 - 8 for threshold value monitoring are set to "0" if the re-

corded value exceeds or drops below a range limit. An entry is added

to the error stack.

Exception: If "automatic reset" type has been selected, no entry will

be added to the error stack.

`

Threshold value monitoring

You can define up to 8 switching thresholds, which can be used to

monitor certain process variables (e.g. different temperature values).

The thresholds can be configured with or without scaling. 2 threshold

values are configured per threshold. One threshold value defines

when the relevant output bit (1 ... 8) is set to "1". The second threshold

value defines when the output bit is reset to "0". No entry is added to

the error stack.

NOTICE

When using the analogue input module for voltage measure-

ment, please note the following:

If the input signal is open circuit or there is a short circuit, this

will not be detected with an input voltage of 0 V. Please use your

risk assessment/hazard analysis to check whether your applica-

tion fulfills the safety-related requirements or whether additional

measures must be taken. We recommend that you configure a

permitted value range between 2 - 10 V PNOZmulti Configurator.