Example: Connection of 5 base units

Example: Connection of 5 base units

6-

Betriebsbereitschaft herstellen Anschlussbeispiel 2

The reaction times are calculated in the same way as application exam-

ple 1. After pressing S1 on Base 1, the semiconductor outputs switch

after the following reaction times t

SUM

:

O0 on Base 1: 69 ms

O1 on Base 3: 104 ms

O0 on Base 4: 139 ms

O0 on Base 5: 104 ms