Preparing for operation

6

Commissioning

6.2.3

Connection examples

Connection examples

6-

6.2.3.1

Example: Series connection of 3 base units

Example: Series connection of 3 base units

6-

Betriebsbereitschaft herstellen Anschlussbeispiel 1

Reaction time t

SUM

between base unit Base 1 and Base 2:

Input delay t

ON

at I3 and I6 + data transmission time1 * t

BUS

through link

module + switch-off delay t

COND

of the semiconductor output at O0

t

SUM

= t

ON

+ (n * t

BUS

) + t

COND

t

SUM

= 4 ms + (1 * 35 ms ) + 30 ms = 69 ms

Reaction time t

SUM

between base unit Base 1 and Base 3:

Input delay t

ON

at I3 und I6 + data transmission time 2 * t

BUS

through link

modules + switch-off delay t

COND

of the semiconductor output at O1

t

SUM

= t

ON

+ (n * t

BUS

) + t

COND

t

SUM

= 4 ms + (2 * 35 ms ) + 30 ms = 104 ms

CHIP-Card

Shield

CHIP-Card

CHIP-Card

Shield

Shield

Shield

S1

K2

K3

I3 I6

O0

O1

Base 1

Base 2

Base 3