8.1

Technical details

8

Technical details

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

8-4

Si-Kennzahlen_Zusatz_Relais_1kan_EN954_Cat2

Requirement on 1-channel relay outputs for Cat. 2 in accordance with

EN 954-1: An additional output switches to a safe condition in the event

of an error or, if that is impossible, signals a hazardous condition.

Si_Kennzahlen_Erläuterung

All the units used within a safety function must be considered when cal-
culating the safety characteristic data.

Technische Daten_Satz Normen

The standards current on 2009-03 apply.

Si-Kennzahlen_Zusatz_Relais_Lebensdauer_BA

The PFH value depends on the switching frequency and the load on the

relay output. If the service life graphs are not accessible, the stated PFH

value can be used irrespective of the switching frequency and the load,

as the PFH value already considers the relay's B10d value as well as the

failure rates of the other components.

relay outputs

single-channel

PL c (Cat. 1)

Cat. 2

-

2.90E-08

20

relay outputs

dual-channel

PL e (Cat. 4)

Cat. 4

SIL CL 3

3.00E-10

20

CAUTION!

It is essential to consider the relay's service life graphs. The relay

outputs' safety-related characteristic data is only valid if the val-

ues in the service life graphs are met.

Output

This manual is related to the following products: