Commissioning, General wiring guidelines, 6commissioning – Pilz PNOZ m0p base unit not expandable User Manual

Page 25: 1 general wiring guidelines

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-1

6.1

General wiring guidelines

6

Commissioning

6

6000

Commissioning

Commissioning

6-

6.1

General wiring guidelines

6100

General wiring guidelines

6-

Verdrahtung_multi_Basis

The wiring is defined in the circuit diagram in the Configurator. There you

can select the inputs that are to perform a particular safety function and

the outputs that will switch this safety function.

Please note:

`

Information given in the “Technical details” must be followed.

`

Outputs:

– O0 to O5 are safety outputs

– O4 and O5 are relay outputs

– O0 to O3 are semiconductor outputs

– OA0 is an auxiliary output.

`

To prevent contact welding, a fuse should be connected before the

output contacts (see technical details).

`

Use copper wire that can withstand 75 °C.

`

Sufficient fuse protection must be provided on all output contacts

with inductive loads.

`

Power for the safety system and input circuits must always be provid-

ed from a single power supply. The power supply must meet the reg-

ulations for extra low voltages with safe separation.

`

Two connection terminals are available for each of the supply con-

nections 24 V and 0 V (semiconductor outputs), plus A1 and A2 (pow-

er supply). This means that the supply voltage can be looped through

several connections. The current at each terminal may not exceed 3

A.

`

Test pulse outputs must exclusively be used to test the inputs. They

must not be used to drive loads.

Do not route the test pulse lines together with actuator cables within

an unprotected multicore cable.

Verdrahtung_multi_Basis_Schaltmatte

`

Test pulse outputs are also used to supply safety mats that trigger a

short circuit.

Test pulses that are used for the safety mat may not be reused for

other purposes.

CAUTION!

DThe plug-in connection terminals on the relay outputs that

carry mains voltage should only be connected and disconnected

when the voltage is switched off.