beautypg.com

8technical details, 1 technical details – Pilz PNOZ m0p base unit not expandable User Manual

Page 40

background image

8.1

Technical details

8

Technical details

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

8-2

Utilisation category in accordance with EN 60947-4-1
Safety contacts: AC1 at 240 V

6.0 A, 1440 VA

Safety contacts: DC1 at 24 V

6.0 A, 144 W

Utilisation category in accordance with EN 60947-5-1
Safety contacts: AC15 at 230 V

3.0 A, 690 W

Safety contacts: DC13 at 24 V (6 cycles/min)

3.0 A, 72 W

Airgap creepage between
relay contacts

3 mm

relay contacts and other safe circuits

5.5 mm

External contact fuse protection (I

K

= 1 kA) to

EN 60947-5-1
Blow-out fuse, quick

6 A

Blow-out fuse, slow

6 A

Circuit breaker 24 VAC/DC, characteristic B/C

6 A

Switch-off delay

50 ms

Auxiliary outputs
Number

1

Switching capability
voltage

24 V

current

0.5 A

power

12.0 W

Galvanic isolation

yes

Short circuit-proof

yes

Residual current at "0"

0.5 mA

Signal level at "1"

UB - 0.5 V DC bei 0.5 A

Cascading output as auxiliary output
Number

1

Switching capability
voltage

24 V

current

0.2 A

power

4.8 W

Galvanic isolation

no

Short circuit-proof

yes

Residual current at "0"

0.5 mA

Environmental data
EMC

EN 60947-5-1

Vibration to EN 60068-2-6
Frequency

10 - 55 Hz

Amplitude

0.35 mm

Climatic suitability

EN 60068-2-78

Airgap creepage in accordance with EN 60664-1
Ambient temperature

0 - 60 °C

Storage temperature

-25 - 70 °C

Mechanical data
Protection type
Mounting (e.g. cabinet)

IP54

Housing

IP20

Terminals

IP20

DIN rail
Top hat rail

35 x 7.5 EN 50022

Recess width

27 mm

Relay outputs