beautypg.com

Preparing for operation, Function test during commissioning, Load project from chip card – Pilz PNOZ m0p base unit not expandable User Manual

Page 29: 6commissioning, 3 preparing for operation, 1 function test during commissioning

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-5

6.3

Preparing for operation

6

Commissioning

6.3

Preparing for operation

6300

Preparing for operation

6-

6.3.1

Function test during commissioning

Function test during commissioning

6-

Verdrahtung_multi_Basis_Betr_Funktionstest_BA

6.3.2

Commissioning the PNOZmulti safety system for the first time

Commissioning the PNOZmulti safety system for the first time

6-

Verdrahtung_multi_Basis_Betr_erstes_Mal_BA

Procedure:

`

Wire the inputs and outputs on the base unit and expansion modules

in accordance with the circuit diagram.

`

Cascading output as auxiliary output: Connect the load to CO+ and

A2, see connection example.

`

Connect the supply voltage:

– Supply voltage for the units (connector X7):

– Terminal A1: + 24 VDC

– Terminal A2: 0 V

– Supply voltage for the semiconductor outputs (connector X2):

– Terminal 24 V: + 24 VDC

– 0V terminal: 0 V

Note: Supply voltage must always be applied to X2 and X7, even if you

are not using the semiconductor outputs.

6.3.2.1

Load project from chip card

Load project from chip card

6-

Verdrahtung_multi_Basis_Betr_erstes_Mal_von_Chipkarte_BA_alt

Procedure:

`

Insert the chip card containing the current project into the card slot on

the base unit.

`

Switch on the supply voltage.

CAUTION!

It is essential to check that the safety devices operate correctly

`

after the chip card has been exchanged

`

after a project has been downloaded

`

when the project has been deleted from the base unit's mem-

ory ("Reset Project" menu)

NOTICE

Chip contacting is only guaranteed if the contact surface is

clean and undamaged. The chip's contact surface should there-

fore be protected from contamination, contact and mechanical

impact such as scratches.