6.2

Preparing for operation

6

Commissioning

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-4

6.2.3

Connection examples

Connection examples

6-

6.2.3.1

Example: Series connection of 3 base units

Example: Series connection of 3 base units

6-

Anschlussbeispiel_Verbindungsmodul_Reihenschalitung_3_Basisgeräte_Text

Reaction time t

SUM

between base unit Base 1 and Base 2:

Input delay t

ON

at I4 and I6 + data transmission time1 * t

BUS

through link

module/interface + switch-off delay t

COND

of the semiconductor output

at O0

t

SUM

= t

ON

+ (n * t

BUS

) + t

COND

t

SUM

= 4 ms + (1 * 35 ms ) + 30 ms = 69 ms

Reaction time t

SUM

between base unit Base 1 and Base 3:

Input delay t

ON

at I4 und I6 + data transmission time 2 * t

BUS

through link

modules/interfaces + switch-off delay t

COND

of the semiconductor out-

put at O1

t

SUM

= t

ON

+ (n * t

BUS

) + t

COND

t

SUM

= 4 ms + (2 * 35 ms ) + 30 ms = 104 ms