background image

4.1

Device properties

4

Function Description

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-2

Connection of multiple base units:

Any number of base units can be connected via link modules. Two link

modules are required for a connection between two base units. Howev-

er, only a maximum of 4 link modules may be connected to any one base

unit.

Data transmission time:

The t

BUS

data transmission time is the time between the virtual output at

base unit 1 being set and the virtual input at base unit 2 becoming avail-

able (see "Technical details").

The maximum reaction time for series connection of n base units

This is the time between the activation of a safety function at the input

on one base unit and the switching of an output on the connected base

unit.

The maximum reaction time t

SUM

includes the following times:

t

ON

: Input delay = 4 ms

t

COND

: Switch-off delay of semiconductor output = 30 ms

t

REL

: Switch-off delay of relay output = 50 ms

t

BUS

: Data transmission time between two base units = 35 ms

n: Number of connections between base units

The maximum reaction time t

SUM

for series connection of n base units

On semiconductor outputs:

tS

UM

= t

ON

+ (n * t

BUS

) + t

COND

On relay outputs:

t

SUM

= t

ON

+ (n * t

BUS

) + t

REL

CAUTION!

For signals that are forwarded or received via the link module, a

calculation must always be made in accordance with the above

formulas.