Probe Tip Termination Notes

For sheath probes, the last inch of the rigid probe is inactive.

The flexible probes terminate with inactive 316SS weights. The weights are insulated
from the probe, and 3/4-16 UNF threads are provided for connection to locally provided
anchoring hardware.

Step 1

At maximum level adjust probe span.

Step 2

At uppermost set point level adjust set point.

Step 3

At second set point level adjust set point 2.

(If

applicable)

Step 4

At third set point level adjust set point 3.

(If

applicable)

Step 5

At fourth set point level adjust set point 4.

(If

applicable)

Combine

At uppermost set point level adjust probe span.

Step 1 & 2

Then: adjust set point 1.

Step 3

At second set point level adjust set point 2

(If

applicable)

Step 4

At third set point adjust set point 3.

(If

applicable)

Step 5

At fourth set point adjust set point 4.

(If

applicable)

Inactive portion
of probe above
probe span

Uppermost set point

Probe Span

Set points can

be position only

within span

Resolution

100%
80%
60%
40%
20%
0%

Maximum level

Probe Span

Set points can

be positioned

anywhere within

span without

resetting

probe span

100%
90 %
80%
70%
60%
50%
40%
30%
20%
10%
0%

Resolution