Actual level set point set up, Calculated set point set up, Model 668 set point set up and output wiring – SOR Multi Point RF Level Switch User Manual
Page 28
28/36
Form 677 (05.13) ©SOR Inc.
Adj
Diff
Set
Point 4
Terminals
Set
Point 1
Terminals
UPPER
LIMIT
RELAY
FAIL SAFE
LOWER
LIMIT
SPAN
RANGE
RELAY
FAIL SAFE
TIME DELA
Y
OFF
ON
LEVEL
ADJUST
ABLE DIFFERENTIAL SET POINT
Set Point 4
Adjust
*Presence LED
*On Delay
*Off Delay
Relay On LED
Fail-safe Hi/Lo
Upper Limit
Presence LED for
Upper Limit
Relay ON LED
Failsafe Hi/Lo
Lower Limit Adjust
Presence LED for
Lower Limit
Set Point 1
Adjust
*Presence LED
*On Delay
*Off Delay
Relay On LED
Fail-safe Hi/Lo
*When the time delay option
is not specifi ed:
Relay On LED functions as
Starred parts not supplied
Adj
Diff
Set
Point 2
Adj. Diff
Terminals
Model 668 Set Point Set up and Output Wiring
Actual Level set point set up
Continued from page 8.
Process level must be steady at set point 1 level. Turn set point 1 adjust pot CW until its
Presence LED lights and then CCW to the point where the LED goes off. Slowly cycle the
Presence LED on and off as required to find the precise threshold at which the LED goes off.
Lower process level to upper limit of the adjustable differential set point. Use the upper
limit (pump up) adjust pot to find the threshold of its Presence LED.
Lower process level to lower limit of the adjustable differential set point. Use the lower
limit (pump down) adjust pot to find the threshold of its Presence LED.
Lower process level to set point 4 level. Use the set point 4 adjust pot to find the
threshold of its Presence LED.
Continue with output wiring from the right side of this page.
Calculated set point set up
Continued from page 9.
The pf value from worksheet line 11 should still be injected. Turn set point 1 adjust pot CW
until its Presence LED lights and then CCW to the point where the LED goes off. Slowly
cycle the LED on and off as required to find the precise threshold at which the LED goes off.
Inject the pf value from line 15 of the worksheet. Use the upper limit (pump up) adjust
pot to find the threshold of its Presence LED.
Inject the pf value from line 17 of the worksheet. Use the lower limit (pump down)
adjust pot to find the threshold of its Presence LED.
Inject the pf value from line 19 of the worksheet. Use the set point 4 adjust pot to find
the threshold of its Presence LED.
Disconnect the probe lead and the probe ground lead from the capacitor substitution box
terminals. Connect the probe lead and the probe ground lead to the probe. Continue with
output wiring from the right side of this page.