Output relay wiring – SOR Multi Point RF Level Switch User Manual

Page 23

background image

Form 677 (05.13) ©SOR Inc.

23/36

Output Relay Wiring

Before connecting the output relay to external devices, determine which failsafe mode is
best suited for the adjustable differential set point. Refer to the continuity chart below when
connecting to the adjustable differential relay terminal strips.

For the adjustable differential set point:
LO mode: When the upper limit is satisfied, the relay turns on. When process level falls below
the lower limit, the relay turns off and remains off until the set point is once again satisfied.
HI mode: When the upper limit is satisfied, the relay turns off. When process level falls below
the lower limit, the relay turns on and remains on until the upper limit is once again satisfied.

Switch

Position

Set Point

Status

Relay

Coil

Relay Continuity

Failsafe

LO/HI

OFF

ON

NC1 C1 NO1 NO2 C2 NC2

NC1 C1 NO1 NO2 C2 NC2

NC1 C1 NO1 NO2 C2 NC2

NC1 C1 NO1 NO2 C2 NC2

ON

OFF

Failsafe

LO/HI

Set
Point

Set
Point

Set
Point

Set
Point