Output Relay Wiring

Before connecting output relays to external devices, determine which failsafe mode is best
suited for each sensing level. Refer to the continuity chart below when connecting to relay
terminal strips.

LO mode: When the set point is satisfied, the relay turns on. When process level falls below
the set point, the relay turns off and remains off until the set point is once again satisfied.
HI mode: When the set point is satisfied, the relay turns off. When process level falls below
the set point, the relay turns on and remains on until set point is once again satisfied.

Switch

Position

Set Point

Status

Relay

Coil

Relay Continuity

OFF

ON

ON

OFF

Failsafe

LO/HI

NC1 C1 NO1 NO2 C2 NC2

NC1 C1 NO1 NO2 C2 NC2

NC1 C1 NO1 NO2 C2 NC2

NC1 C1 NO1 NO2 C2 NC2

Failsafe

LO/HI

Set

Point

Set

Point

Set

Point

Set

Point

Time Delay Adjustments

Set points 1 and 2 may be equipped with time delay adjustments. Both on delay and off
delay are one turn pots.
On Delay: Length of time that set point must be satisfied before the output relay reacts.
Off Delay: Length of time that process must be below set point before the output relay reacts.
Adjustment pot fully CCW = 0 second delay
Adjustment pot fully CW = 30 second delay (approximate)