beautypg.com

Time delay adjustments – SOR Multi Point RF Level Switch User Manual

Page 21

background image

Form 677 (05.13) ©SOR Inc.

21/36

Output Relay Wiring
Before connecting output relays to external devices, determine which failsafe mode is best
suited for each sensing level. Refer to the continuity chart below when connecting to relay
terminal strips.

LO mode: When the set point is satisfied, the relay turns on. When process level falls below
the set point, the relay turns off and remains off until the set point is once again satisfied.
HI mode: When the set point is satisfied, the relay turns off. When process level falls below
the set point, the relay turns on and remains on until set point is once again satisfied.

Time Delay Adjustments

Set points 1, 2, 3 and 4 may be equipped with time delay adjustments. Both on delay and
off delay are one turn pots.
On Delay: Length of time that set point must be satisfied before the output relay reacts.
Off Delay: Length of time that process must be below set point before the output relay reacts.
Adjustment pot fully CCW = 0-second delay
Adjustment pot fully CW = 30-second delay (approximate)

Switch

Position

Set Point

Status

Relay

Coil

Relay Continuity

Failsafe

LO/HI

OFF

ON

NC1 C1 NO1 NO2 C2 NC2

NC1 C1 NO1 NO2 C2 NC2

NC1 C1 NO1 NO2 C2 NC2

NC1 C1 NO1 NO2 C2 NC2

ON

OFF

Failsafe

LO/HI

Set
Point

Set
Point

Set
Point

Set
Point