Actual level set point set up, Calculated set point set up, Model 665 set point set up and output wiring – SOR Multi Point RF Level Switch User Manual
Page 22
22/36
Form 677 (05.13) ©SOR Inc.
Model 665 Set Point Set up and Output Wiring
UPPER
LIMIT
LOWER
LIMIT
RANGE
SPAN
Upper Limit Adjust
Presence LED
for Upper
Relay On LED
Failsafe Hi/Lo
Presence LED
for Lower
Lower Limit Adjust
Set Point
2 Adj. Diff
Adj
Diff
RELAY
FAIL SAFE
ADJUST
ABLE DIFFERENTIAL SET POINT
Actual Level set point set up
Continued from page 8.
Process level must be steady at upper limit of adjustable dead band.
Turn upper limit (pump up) adjust pot CW until its Presence LED lights and then CCW to
the point where the LED goes off. Slowly cycle the Presence LED on and off as required to
find the precise threshold at which the LED goes off.
Lower process level to lower limit. Use the lower limit (pump down) adjust pot to find
the threshold of its Presence LED. Continue with output wiring on the next page.
Calculated set point set up
Continued from page 9.
The pf value from worksheet line 11 should still be injected.
Turn the upper limit (pump up) adjust pot CW until its Presence LED lights and then CCW
to the point where the LED goes off.
Slowly cycle the LED on and off as required to find the precise threshold at which the
LED goes off.
Inject the pf value from line 15 of the worksheet. Use the lower limit (pump down)
adjust pot to find the threshold of its Presence LED. Disconnect the probe lead and the
probe ground lead to the probe. Continue with output wiring on the next page.
*When the time delay
option is not specified:
Relay On LED functions
as Presence LED
Starred parts not supplied