Actual level set point set up, Calculated set point set up, Output relay wiring – SOR Multi Point RF Level Switch User Manual
Page 24: Model 666 set point set up and output wiring
24/36
Form 677 (05.13) ©SOR Inc.
Model 666 Set Point Set up and Output Wiring
Set Point 1
Upper Limit Adjust
*Presence LED
*On Delay
*Off Delay
Relay On LED
Failsafe Hi/Lo
Upper Limit Adjust
Presence LED
for Upper Limit
Relay On LED
Failsafe Hi/Lo
Lower Limit Adjust
Presence LED for
Lower Limit
Set
Point 1
Terminals
Set Point 2
Adj. Diff
Terminals
Adj
Diff
UPPER
LIMIT
RELAY
FAIL
SAFE
TIME DELA
Y
OFF
ON
LOWER
LIMIT
LEVEL
SET POINT #1
RANGE
SPAN
ADJUST
ABLE DIFFERENTIAL SET POINT
Actual Level set point set up
Continued from page 8.
Process level must be steady at set point 1 level. Turn set point 1 adjust pot CW until its
Presence LED lights and then CCW to the point where the LED goes off. Slowly cycle the
Presence LED on and off as required to find the precise threshold at which the LED goes off.
Lower process level to upper limit. Use the upper limit (pump up) adjust pot to find the
threshold of its Presence LED.
Lower process level to lower limit. Use the lower limit (pump down) adjust pot to find
the threshold of its Presence LED.
Calculated set point set up
Continued from page 9.
The pf value from worksheet line 11 should still be injected. Turn set point 1 adjust pot CW
until its Presence LED lights and then CCW to the point where the LED goes off. Slowly
cycle the LED on and off as required to find the precise threshold at which the LED goes off.
Inject the pf value from line 15 of the worksheet. Use the upper limit (pump up) adjust
pot to find the threshold of its Presence LED.
Inject the pf value from line 17 of the worksheet. Use the lower limit (pump down)
adjust pot to find the threshold of its Presence LED.
Disconnect the probe lead and the probe ground lead from the capacitor substitution box
terminals. Connect the probe lead and the probe ground lead to the probe. Continue with
output wiring from the right side of this page.
Output Relay Wiring
Before connecting output relays to external devices, determine which failsafe mode is best
suited for each sensing level. Refer to the continuity chart below when connecting to relay
terminal strips.
*When the time delay
option is not specified:
Relay On LED
functions
as
Presence
LED
Starred parts
not
supplied