Actual level set point set up, Calculated set point set up, Model 664 set point set up and output wiring – SOR Multi Point RF Level Switch User Manual
Page 20
20/36
Form 677 (05.13) ©SOR Inc.
Model 664 Set Point Set up and Output Wiring
Actual Level set point set up
Continued from page 8.
Process level must be steady at set point 1 level. Turn set point 1 adjust pot CW until its
Presence LED lights and then CCW to the point where the LED goes off. Slowly cycle the
Presence LED on and off as required to find the precise threshold at which the LED goes off.
Lower process level to set point 2 level. Use the set point 2 adjust pot to find the
threshold of its Presence LED.
Lower process level to set point 3 level. Use set point 3 adjust pot to find the threshold
of its Presence LED.
Lower process level to set point 4 level. Use the set point 4 adjust pot to find the
threshold of its Presence LED. Continue with output wiring on the next page.
Calculated set point set up
Continued from page 9.
The pf value from worksheet line 11 should still be injected. Turn set point 1 adjust pot CW
until its Presence LED lights and then CCW to the point where the LED goes off. Slowly
cycle the LED on and off as required to find the precise threshold at which the LED goes off.
Inject the pf value from line 15 of the worksheet. Use the upper limit (pump up) adjust
pot to find the threshold of its Presence LED.
Inject the pf value from line 17 of the worksheet. Use the lower limit (pump down)
adjust pot to find the threshold of its Presence LED.
Inject the pf value from line 19 of the worksheet. Use the set point 4 adjust pot to find
the threshold of its Presence LED.
Disconnect the probe lead and the probe ground lead from the capacitor substitution box
terminals. Connect the probe lead and the probe ground lead to the probe. Continue with
output wiring on the next page.
Adjust
Presence LED*
On Delay*
Off Delay*
Relay On LED
Failsafe Hi/Lo
Adjust
Presence LED*
On Delay*
Off Delay*
Relay On LED
Failsafe Hi/Lo
Adjust
Presence LED*
On Delay*
Off Delay*
Relay On LED
Failsafe Hi/Lo
Adjust
Presence LED*
On Delay*
Off Delay*
Relay On LED
Failsafe Hi/Lo
Set Point 1
Set Point 4
Set Point 3
Set
Point 3
Terminals
Set
Point 2
Terminals
Set Point 2
LEVEL
LEVEL
OFF
ON
OFF
ON
SET POINT #1
TIME DELA
Y
LEVEL
LEVEL
OFF
ON
OFF
ON
SET POINT #4
SET POINT #3
RELAY
FAILSAFE
RANGE
RELAY
FAILSAFE
RELAY
FAILSAFE
RELAY
FAILSAFE
TIME DELA
Y
TIME DELA
Y
TIME DELA
Y
SET POINT #2
SPAN
Set
Point 4
Terminals
Set
Point 1
Terminals
*When the time delay
option is not specified:
Relay On LED
functions
as
Presence
LED
Starred parts
not
supplied