beautypg.com

Worksheet sample, Calculated set up – SOR Multi Point RF Level Switch User Manual

Page 13

background image

Form 677 (05.13) ©SOR Inc.

13/36

Calculated Set up

 Vessel Level A

 Vessel Level B

 Line 1 - Line 2

-

=

 Capacitance @ Level A

pf

 Capacitance @ Level B

pf

 Line 4 - Line 5

-

=

pf

 Line 6 ÷ Line 3

÷

=

pf

Maximum

Level

 Line 8 - Line 1

-

=

 Line 9 x Line 7

x

=

pf

Line 10 + Line 7

+

=

pf

Line 8 x Line 7

x

=

pf

Line 11 - Line 12

-

=

pf

For 661-664, 666, 668 enter set point 1

For 665, 667 enter upper limit of adjustable differential

(Line 14 x Line 7) + Line 1

(

x

) +

=

pf

For 662-664 enter set point 2

For 666, 668 enter upper limit of adjustable differential

For 665, 667 enter lower limit of adjustable differential

(Line 16 x Line 7) + Line 13

(

x

) +

=

pf

For 663, 664 enter set point 3

For 666, 668 enter lower limit of adjustable differential

For 667 enter set point 4

(Line 18 x Line 7) + Line 13

(

x

) +

= 2500

pf

For 664, 668 enter set point 4

21

(Line 20 x 7) + Line 13

(

x

) +

=

pf

Vessel Level A . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10 ft.

Vessel Level B . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8 ft.

Line 1 - Line 2 . . . . . . . . . . . . . . . . . . . . . . . .

10 - 8 = 2 ft.

Capacitance @ Level A . . . . . . . . . . . . . . . . . . . . . .

2200 pf

Capacitance @ Level B . . . . . . . . . . . . . . . . . . . . . .

1900 pf

Line 4 - Line 5 . . . . . . . . . . . . . . . . . . .

2200 - 1900 = 300 pf

Line 6 ÷ Line 3. . . . . . . . . . . . . . . . . . . .

300 ÷ 2 = 150 pf/ft.

Maximum Level . . . . . . . . . . . . . . . . . . . . . . . . . . . .

30 ft.

Line 8 - Line 1 . . . . . . . . . . . . . . . . . . . . . . .

30 - 10 = 20 ft.

Line 9 x Line 7 . . . . . . . . . . . . . . . . . . . .

20 - 150 = 3000 pf

Line 10 + Line 7

. . . . . . . . . . . . . . . . . . .

20 x 150 = 3000 pf

Line 8 x Line 7

. . . . . . . . . . . . . . . . . . . .

30 x 150 = 4500 pf

Line 11 - Line 12

. . . . . . . . . . . . . . . . .

5200 - 4500 = 700 pf

For 661-664, 666, 668 enter set point 1

. . . . . . . . . . . . . .

25 ft.

For 665, 667 enter upper limit of adjustable differential

(Line 14 x Line 7) + Line 13

. . . . . . . (25 x 150) + 700 = 4450 pf

For 662-664 enter set point 2

. . . . . . . . . . . . . . . . . . . .

20 ft.

For 666, 668 enter upper limit of adjustable differential

For 665, 667 enter lower limit of adjustable differential

(Line 16 x Line 7) + Line 13

. . . . . . . (20 x 150) + 700 = 3700 pf

For 663, 664 enter set point 3

. . . . . . . . . . . . . . . . . . . .

12 ft.

For 666, 668 enter lower limit of adjustable differential

For 667 enter set point 4

(Line 18 x Line 7) + Line 13

. . . . . . . (12 x 150) + 700 = 2500 pf

For 664, 668 enter set point 4

. . . . . . . . . . . . . . . . . . . .

7 ft.

21

(Line 20 x 7) + Line 13

. . . . . . . . . . . (7 x 150) + 700 = 1750 pf

Worksheet
Sample