beautypg.com

SOR 1540 Side Mounted Non-Bleed Pneumatic Level Switch User Manual

Pneumatic level switch, 1540 side mounted, General instructions

background image

Form 1306 (04.13) ©SOR Inc.

1/4

1540 Side Mounted

Pneumatic Level Switch

General Instructions

Registered Quality System to ISO 9001

NOTE: If you suspect that a product is defective, contact the factory or the SOR Representative
in your area for a return authorization number (RMA). This product should only be installed by
trained and competent personnel.

The side mounted SOR

®

1540 Pneumatic Level

Switch provides a pneumatic output signal for either

Design and specifications are subject to change without notice.

For latest revision, go to www.sorinc.com

a high or low level condition.
The float moves a magnet
into the field of a
magnetically actuated
sensor. The unit may
be mounted for either
high or low liquid level alarm.

Before Installing the Level Switch

 Inspect the unit for any shipment damage.
 Check for mechanical clearance. The float must move freely throughout its stroke inside

the vessel.

 Use an acceptable thread compound to ensure a leak-free fit and avoid thread

galling when installing the unit into the vessel.

 Clean, dry air or gas must be used as the supply media to avoid plugging critical

internal restrictions.

 MC or MD (manual check) option can be removed to allow supply fitting to be installed.

Reseal threads with acceptable thread compound and insert to dimension shown.

SUPPLY PRESSURE RANGE:

J0 SWITCH – 0-30 psi (0-2 BAR)

J1 SWITCH – 0-80 psi (0-5.5 BAR)

at a product is defective, contact the factory or the SOR Representative

R

®

1540 Pneumatic Level

umatic output signal for either

dition.

net

alarm.