Appendix A: Wiring

Discrete Output Wiring

The RMC150E, DI/O and UI/O outputs are solid state relays. When off,
they have high impedance, and when on, they have low impedance.

When switching inductive loads, place a diode or tranzorb across the
load to protect the switch when it turns off. Otherwise, a voltage spike
in excess of the 30 V rating of the SSR may occur. See the RMC150E
Discrete I/O Wiring
topic in the RMCTools help for more details.

DI/O and UI/O Module

Outputs can be wired in either a high-side or low-side configuration.
Because all the outputs share a common, all outputs on the same
module must be wired the same.


RMC150E Module

Each output has a “+” and “–” connection. Outputs can be wired in
either a high-side or low-side configuration.

RMC150E

DI/O

UI/O

On Impedance

50Ω max, 25Ω typical

Max Current

75 mA

(50 mA for Class I Div 2)

75 mA

(Class I Div 2 not available)

Max Voltage

30 V

RMC150E

Resistive

load

+VCC (12-24 VDC)

Output +

Output -

RMC150E

+VCC (12-24 VDC)

Output +

Output -

Resistive

load

RMC Module

+VCC (12-24 VDC)

Output
Output

Resistive

Load

Output Cmn

RMC Module

+VCC (12-24 VDC)

Output
Output

Resistive

Load

Output Cmn