Setting the water level & bleed rate, Controls – installation / setup / commissioning – Bonaire Touchpad User Manual
Page 45

M
ULTI
-A
PPLIANCE
T
OUCH
P
AD
Controls – Installation / Setup / Commissioning
Setting the Water Management Systems Parameter Table.
To enter into the installer setup mode for the water management options use the following steps.
Step 1
Ensure the control is in the OFF
mode.
Step 2
A series of unseen icons must be
pressed
1. Press and hold the ZONE 4 (1) icon
allowing for a Triple BEEP followed by a
Single BEEP.
2. In quick succession press the unseen
APPLIANCE COOL (2) icon followed by
the HEAT (3) icon.
3. If successfully executed the area will
display tP:01.
4. If unsuccessful repeat 1 and 2 of STEP 2.
Step 3 Using
the
to
select
E:01 from the display
area.
Step 4
Press ENTER. The display will now change to 1:01.
Step 5
Using the
arrows, select the parameter to
be changed as per the Water Management Table. Press
ENTER.
Step 6
Using the
to change the value as per the
‘Water Management Table”. Press ENTER.
Step 7
To change more water management parameters repeat
Step 4 – 7.
Step 8
Press FINISH to exit.
Where multiple units have been connected to a single touchpad, this procedure will have to be repeated for
each of the units connected – E01, E02 etc.
S
ETTING THE
W
ATER
L
EVEL
&
B
LEED RATE
There are 3 diagnostic modes available for use of which Parameter 2 and 3 can be used to assist the
setting of water levels in the unit. See the table below.
Diagnostic Table
Installer Maintenance
Parameter
Value Duration
1
Rt
_ _ _ _ x 100
Unit Run Time
2
00
10 Minutes
Fill Valve
3
00
20 Minutes
Fill Valve & Pump
Bonaire Control Systems
Page 45