Combustion air pressure system failure, Check combustion fan ok. service call, Slow closing gas valve – Bonaire Touchpad User Manual
Page 42: Reset, service call, Controls – installation / setup / commissioning

M
ULTI
-A
PPLIANCE
T
OUCH
P
AD
Controls – Installation / Setup / Commissioning
F
AULT
C
ODES
F
OR
H
IGH
E
FFICIENCY
,
M
ID
E
FFICIENCY
H
EATERS
Code No.
Fault Code
Diagnosis
00
No Activity
There has been no fault codes registered or the
control has not been coded to the unit.
01
Block Flue
Check flue cowl installed correctly
02
Pressure Switch fused closed
Service Call
03
Combustion air pressure system failure
Check combustion fan OK. Service call.
04
Room air over temperature (auto reset)
Check Minimum Fan Speed, Duct design
05
Controller electronic malfunction
Reset, Service Call
06
Slow closing gas valve
Reset, Service Call
07
Ignition failure
Check: - igniter works, flame sensor, gas supply. For
forced draft High Efficiency units also check blocked
flue and blocked condensate drain. Service Call
08
Gas Interruption
Check gas supply, Flame Sensor, Service Call
09
EEPROM failure
Reset, Service Call
11
Missed Transmission
Check loom integrity and connections
12
No Communication (Touch Pad Only)
Touchpad cannot detect unit – check loom integrity
and connections
15
No recorded fault codes