MODEL

A

B

C

D

R

3

12

5

42

TABLE 2: ALCOVE CLEARANCES, IN INCHES, REFER TO FIGURE 3

3

If a Model R is to be installed in an Alcove, contact a local building professional or building inspector to
obtain information on any local code requirements for such installation.

FLOOR PROTECTION REQUIREMENTS

1. All Country Flame freestanding catalytic woodstoves require a listed floor protector that is noncombustible.

Country Flame catalytic stoves were tested with a listed floor protection that had a thermal conductivity of K =
0.85 BTU-inch per hour per square foot per degree Fahrenheit and that was 3/8” thick (9.5mm) non-asbestos
millboard. Refer to FIGURE 4 and TABLE 4 for floor protector information.

FIGURE 4: FLOOR PROTECTOR DIMENSIONS

NOTE: Chimney connectors must have 2 inches of floor protection from all sides in all direction.

MODEL

BBF

B

R

G

8 8 8

H

18 18 16

I

8 8 3

TABLE 3: FLOOR PROTECTOR, IN INCHES, REFERS TO FIGURE 4

2. If a floor protector, different from the tested floor protector, is to be used, it must meet or exceed the requirements of

the listed R-value of the tested floor protector. To convert alternate floor protectors to their respective R value use the
following procedures:

a. Convert floor material specification to R-value.

i.

R-value is given – no conversion is required.

ii.

k-factor is given with required thickness (T) in inches: R = (1/k) x T.

iii.

C-factor given: R = 1/C.