beautypg.com

Viconics VWZS Integration Guide User Manual

Page 61

background image

61

Object

Index Range Restrictions

Minimum On/Off Time ( Anticycle )

1

0 Minutes

2

1 Minute

3

2 Minutes

4

3 Minutes

5

4 Minutes

6

5 Minutes

Event Display

1

2 Events

2

4 Events

Heating Stages
Cooling Stages

1

1 Stage

2

2 Stages

Network Handle

1

Default Zone Handle

2

Default Minus Occupancy

3

Full Release

Occupancy Command

1

Local Occupancy

2

Occupied

3

Unoccupied

On Off Control CPH

1

3 CPH

2

4 CPH

3

5 CPH

4

6 CPH

5

7 CPH

6

8 CPH

Output #1 Configuration ( VT72xx )

1

One Output

2

Separate Outputs

PI Cooling Weight
PI Heating Weight

1

0%

2

25%

3

50%

4

75%

5

100%

Pipe Number

1

Two Pipes

2

Four Pipes

Proportional Band ( VT76xx )

1

3 ºF / 1.7 ºC

2

4 ºF / 2.2 ºC

3

5 ºF / 2.8 ºC

4

6 ºF / 3.3 ºC

5

7 ºF / 3.9 ºC

6

8 ºF / 4.4 ºC

7

9 ºF / 5.0 ºC

8

10 ºF / 5.6 ºC